Our Datacenter
| Data Centre Basics
Data Centre Location: Crockford St, Port Melbourne, Victoria Secure Racks Used: APC AR3100 (1070mm) Power Distribution Units: APC AP7952 Switched & Metered
Power Specifications
- Minimum N+1 Redundancy on Power Supply
- Diverse A&B Feeds via 60KVA & 120KVA UPS Systems (N+1), Backup Batteries
- 750KVA Backup Generator, Onsite Fuel Storage for 2 Days Runtime (4 Hours Contract for Further Fuel Provision)
Controlled Environment
- Minimum N+1 Redundancy on Air Conditioning
- 60KW Air Conditioning Units (N+1)
- Temperatures Maintained at 22ºC (+/- 2ºC)
- Humidity Maintained at 50% (+/- 10%)
- Environmental Monitoring
Fire Detection and Suppression
- VESDA Fire Detection
- FM200 Gas Fire Suppression System
Data Centre Security & Access
- Access Control via Proximity Cards & Biometrics
- CCTV Camera Monitoring
- Onsite Security Staff